Effect of Using PLL-Based Grid-Forming Control on Active Power Dynamics Under Various SCR
Communication avec acte
Author
ROKROK, Ebrahim
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
QORIA, Taoufik
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
BRUYERE, Antoine
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
Date
2019Abstract
This paper investigates the effect of using phaselocked loop (PLL) on the performance of a grid-forming controlled converter. Usually, a grid-forming controlled converter operates without dedicated PLL. It is shown that in this case, the active power dominant dynamics are highly dependent to the grid short circuit ratio (SCR). In case of using PLL, the obtained results illustrate that the SCR has a negligible effect on the dynamic behavior of the system. Moreover, the power converter will not participate to the frequency regulation anymore; therefore, the converter response time can be adjusted independently to the choice of the droop control gain, which is not possible without PLL. A simple equivalent model is presented which gives a physical explanation of these features.
Files in this item
Related items
Showing items related by title, author, creator and subject.
-
Communication avec acteQORIA, Taoufik; COLAS, Frédéric; GUILLAUD, Xavier; DEBRY, Marie-Sophie; PREVOST, Thierry; GRUSON, Francois (IEEE, 2018)From the origin of the grid, energy has been delivered to electrical loads mainly by synchronous machines. All the main rules to manage the grid have been based on the electromechanical behavior of these machines which ...
-
Article dans une revue avec comité de lectureQORIA, Taoufik; COLAS, Frédéric; DENIS, Guillaume; PREVOST, Thibault; GUILLAUD, Xavier; GRUSON, Francois (Institute of Electrical and Electronics Engineers, 2019)The present paper deals with the post-fault synchronization of a voltage source converter based on the droop control. In case of large disturbances on the grid, the current is limited via current limitation algorithms such ...
-
Article dans une revue avec comité de lectureLI, Chuanyue; QORIA, Taoufik; COLAS, Frédéric; JUN, Liang; WENLONG, Ming; GUILLAUD, X.; GRUSON, Francois (MDPI, 2019)The dq impedance stability analysis for a grid-connected current-control inverter is based on the impedance ratio matrix. However, the coupled matrix brings difficulties in deriving its eigenvalues for the analysis based ...
-
Communication avec acteQORIA, Taoufik; LI, Chuanyue; OUE, Ko; COLAS, Frédéric; GUILLAUD, Xavier; PREVOST, Thibault (IEEE PES PowerTech 2019, 2019)In the near future, power converters will be massively introduced in transmission grids due to renewable energy sources and high voltage direct current (HVDC) increase. Voltage Source Converter (VSC) control laws assume ...
-
Communication avec acteQORIA, Taoufik; PREVOST, Thibault; DENIS, Guillaume; COLAS, Frédéric; GUILLAUD, Xavier (EPE'19 ICCE EUROPE, 2019)Because of the throng of control strategies based Voltage Source Converters (VSC) recently proposed in the literature; their classification and characterization are becoming a trending topic. The high similarities of the ...