Critical clearing time determination and enhancement of grid-forming converters embedding virtual impedance as current limitation algorithm
Article dans une revue avec comité de lecture
Date
2019Journal
IEEE Journal of Emerging and Selected Topics in Power ElectronicsAbstract
The present paper deals with the post-fault synchronization of a voltage source converter based on the droop control. In case of large disturbances on the grid, the current is limited via current limitation algorithms such as the virtual impedance. During the fault, the power converter internal frequency deviates resulting in a converter angle divergence. Thereby, the system may lose the synchronism after fault clearing and which may lead to instability. Hence, this paper proposes a theoretical approach to explain the dynamic behavior of the grid forming converter subject to a three phase bolted fault. A literal expression of the critical clearing time is defined. Due to the precise analysis of the phenomenon, a simple algorithm can be derived to enhance the transient stability. It is based on adaptive gain included in the droop control. These objectives have been achieved with no external information and without switching from one control to the other. To prove the effectiveness of the developed control, experimental test cases have been performed in different faulted conditions.
Files in this item
Related items
Showing items related by title, author, creator and subject.
-
Communication avec acteQORIA, Taoufik; PREVOST, Thibault; DENIS, Guillaume; COLAS, Frédéric; GUILLAUD, Xavier (EPE'19 ICCE EUROPE, 2019)Because of the throng of control strategies based Voltage Source Converters (VSC) recently proposed in the literature; their classification and characterization are becoming a trending topic. The high similarities of the ...
-
Article dans une revue avec comité de lectureQORIA, Taoufik; COLAS, Frédéric; DENIS, Guillaume; PREVOST, Thibault; GUILLAUD, Xavier (Institute of Electrical and Electronics Engineers, 2019)The present paper deals with the post-fault synchronization of a voltage source converter based on the droop control. In case of large disturbances on the grid, the current is limited via current limitation algorithms such ...
-
Communication avec acteQORIA, Taoufik; COLAS, Frédéric; GUILLAUD, Xavier; DEBRY, Marie-Sophie; PREVOST, Thierry; GRUSON, Francois (IEEE, 2018)From the origin of the grid, energy has been delivered to electrical loads mainly by synchronous machines. All the main rules to manage the grid have been based on the electromechanical behavior of these machines which ...
-
Communication avec acteQORIA, Taoufik; COLAS, Frédéric; DENIS, Guillaume; PREVOST, T.; GUILLAUD, Xavier (2019)The virtual synchronous machine concept (VSM) has been developed initially to reproduce the synchronous machine stabilizing effect by providing inertia with the emulation of swing equation, whereas droop control is developed ...
-
Communication avec acteQORIA, Taoufik; LI, Chuanyue; OUE, Ko; COLAS, Frédéric; GUILLAUD, Xavier; PREVOST, Thibault (IEEE PES PowerTech 2019, 2019)In the near future, power converters will be massively introduced in transmission grids due to renewable energy sources and high voltage direct current (HVDC) increase. Voltage Source Converter (VSC) control laws assume ...