Direct AC Voltage Control for Grid-Forming Inverters

Article dans une revue avec comité de lecture
Auteur
QORAI, Taoufik
LI, Chuanyue
OUE, Ko
COLAS, Frédéric
GUILLAUD, Xavier
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]
ccGRUSON, Francois
13338 Laboratoire d’Électrotechnique et d’Électronique de Puissance - ULR 2697 [L2EP]

URI
http://hdl.handle.net/10985/17961
DOI
10.1007/s43236-019-00015-4
Date
2019
Journal
Journal of Power Electronics

Résumé

Grid-forming inverters usually use inner cascaded controllers to regulate output AC voltage and converter output current. However, at the power transmission system level where the power inverter bandwidth is limited, i.e., low switching frequency, it is difcult to tune controller parameters to achieve the desired performances because of control loop interactions. In this paper, a direct AC voltage control-based state-feedback control is applied. Its control gains are tuned using a linear quadratic regulator. In addition, a sensitivity analysis is proposed to choose the right cost factors that allow the system to achieve the imposed specifcations. Conventionally, a system based on direct AC voltage control has no restriction on the inverter current. Hence, in this paper, a threshold virtual impedance has been added to the state-feedback control in order to protect the inverter against overcurrent. The robustness of the proposed control is assessed for diferent short-circuit ratios using smallsignal stability analysis. Then, it is checked in diferent grid topologies using time domain simulations. An experimental test bench is developed in order to validate the proposed control.

Fichier(s) constituant cette publication

Nom:
L2EP_JPE_2019_QORIA.pdf
Taille:
3.777Mo
Format:
PDF
Voir/Ouvrir

Cette publication figure dans le(s) laboratoire(s) suivant(s)

  • Laboratoire d'Electrotechnique et d'Electronique de Puissance (L2EP) de Lille

Documents liés

Visualiser des documents liés par titre, auteur, créateur et sujet.

  • Coupling Influence on the dq Impedance Stability Analysis for the Three-Phase Grid-Connected Inverter 
    Article dans une revue avec comité de lecture
    LI, Chuanyue; QORIA, Taoufik; COLAS, Frédéric; JUN, Liang; WENLONG, Ming; GUILLAUD, X.; ccGRUSON, Francois (MDPI, 2019)
    The dq impedance stability analysis for a grid-connected current-control inverter is based on the impedance ratio matrix. However, the coupled matrix brings difficulties in deriving its eigenvalues for the analysis based ...
  • Tuning of Cascaded Controllers for Robust Grid-Forming Voltage Source Converter 
    Communication avec acte
    QORIA, Taoufik; COLAS, Frédéric; GUILLAUD, Xavier; DEBRY, Marie-Sophie; PREVOST, Thierry; ccGRUSON, Francois (IEEE, 2018)
    From the origin of the grid, energy has been delivered to electrical loads mainly by synchronous machines. All the main rules to manage the grid have been based on the electromechanical behavior of these machines which ...
  • Tuning of Cascaded Controllers for Robust Grid-Forming Voltage Source Converter 
    Communication avec acte
    QORAI, Taoufik; GRUSON, François; COLAS, Frédéric; GUILLAUD, Xavier; DEBRY, M.-S.; PREVOST, T. (IEEE, 2018-06)
    From the origin of the grid, energy has been delivered to electrical loads mainly by synchronous machines. All the main rules to manage the grid have been based on the electromechanical behavior of these machines which ...
  • Critical clearing time determination and enhancement of grid-forming converters embedding virtual impedance as current limitation algorithm 
    Article dans une revue avec comité de lecture
    QORIA, Taoufik; COLAS, Frédéric; DENIS, Guillaume; PREVOST, Thibault; GUILLAUD, Xavier; ccGRUSON, Francois (Institute of Electrical and Electronics Engineers, 2019)
    The present paper deals with the post-fault synchronization of a voltage source converter based on the droop control. In case of large disturbances on the grid, the current is limited via current limitation algorithms such ...
  • Full State Regulation of the Modular Multilevel DC converter (M2DC) achieving minimization of circulating currents 
    Article dans une revue avec comité de lecture
    LI, Yafang; DELARUE, Philippe; LE MOIGNE, Philippe; COLAS, Frédéric; GUILLAUD, Xavier; ccGRUSON, Francois (Institute of Electrical and Electronics Engineers, 2019)
    The M2DC exploits the interleaving between the three legs of an MMC to realize a promising uninsulated DC/DC converter to interconnect HVDC grids. This paper details a current and energies decoupled model of the M2DC. The ...

Parcourir

Tout SAMLaboratoiresAuteursDates de publicationCampus/InstitutsCe LaboratoireAuteursDates de publicationCampus/Instituts

Lettre Diffuser la Science

Dernière lettreVoir plus

Statistiques de consultation

Publications les plus consultéesStatistiques par paysAuteurs les plus consultés

ÉCOLE NATIONALE SUPERIEURE D'ARTS ET METIERS

  • Contact
  • Mentions légales

ÉCOLE NATIONALE SUPERIEURE D'ARTS ET METIERS

  • Contact
  • Mentions légales